i am seeking advice, all safety procedures will be followed, along with an abundance of common sense …….
I am only doing the conduits and running wire now, not any hookups.
I will be installing an RV outlet on the side of my house. Conduit is sealed 1″ PVC. Length from panel to outlet is approx 25′. Needs are a 50amp RV outlet, along with a 20amp GFI outlet. I will most likely use an RV style service panel that has both outlets and breakers, similar to those in a campground. I will run a conduit out of panel and buried for any future needs.
?? What size wire is needed. I am thinking #4.. with a 70amp breaker
THANKS Crew !!!!!!!
[External image (uploads.tapatalk-cdn.com), not copied]
4AWG based on the info you provided.
RickyMcGrath wrote:
14 minutes ago, RickyMcGrath said:[External image (uploads.tapatalk-cdn.com), not copied]
4AWG based on the info you provided.
Thanks Ricky !!!
what app is that, please ?
Foneguy wrote:
Thanks Ricky !!!what app is that, please ?
DeWalt Mobile Pro.
It has 145 different calculators pertinent to construction. It’s pretty handy.
RickyMcGrath wrote:
4 minutes ago, RickyMcGrath said:It has 145 different calculators pertinent to construction. It’s pretty handy.
HAH !!!! Now I feel like a dumb ass !!!
i have that app…….
thanks for the help
Looks like you added the electricians calculator pack ?
i will use this more often now …..
RickyMcGrath wrote:
It has 145 different calculators pertinent to construction. It’s pretty handy.
I love that app
Foneguy wrote:
Looks like you added the electricians calculator pack ?i will use this more often now …..
I added the full master pack with all calculators.
That is F-ing awesome! DL the app now, thanks
BMack37 wrote:
That is F-ing awesome! DL the app now, thanks
You will have to pay for different calculations, best bet buy them all!
[External image (uploads.tapatalk-cdn.com), not copied]
[External image (uploads.tapatalk-cdn.com), not copied]
[External image (uploads.tapatalk-cdn.com), not copied]
You may be better off running 3/2 Al. 70A is a weird size and #4 copper isn’t a common commodity. With 3/2 Al you can get NMD and strip off the jacket or run 3/2 ACWU. In any case a 1″ conduit may be an unpleasant pull as I’m guessing you have 2 90s? A 20′ U? 4 is as big as you can go in 1″ pipe so if you could do 1.25″ it would go smoother.
Sent from my SM-G930W8 using Tapatalk
noops wrote:
You may be better off running 3/2 Al. 70A is a weird size and #4 copper isn’t a common commodity. With 3/2 Al you can get NMD and strip off the jacket or run 3/2 ACWU. In any case a 1″ conduit may be an unpleasant pull as I’m guessing you have 2 90s? A 20′ U? 4 is as big as you can go in 1″ pipe so if you could do 1.25″ it would go smoother.Sent from my SM-G930W8 using Tapatalk
Most Lowes and HD carry 4AWG THHN by the foot. For a short run…..
RickyMcGrath wrote:
9 hours ago, RickyMcGrath said:Most Lowes and HD carry 4AWG THHN by the foot. For a short run…..
I did a little re-engineering in my head… My needs were a lot less than I planned for, so I picked up some #6 …
wire not pulled yet, but I a sure this is going to be fine …
thought I had a pic, will post it later